meet go

Intelligent Control, Simple Commissioning

Intelligent Control Made Simple

..

..

...

APPLICATIONS

Multiple Applications, Multiple Configurations

..

...

Feature Rich Solutions

..

..

...

Technical Data

Prolojik Go™

Go™ is the next generation of Prolojik’s lighting control. Go™ takes lighting control from the domain of specialist engineers and makes it available to installers and end- users without compromising on functionality.


// FEATURES////////////////////////////////////////////////////////////////////////////////////////////////

  • 9 port LCM, with 3 switching relays groups
  • Fully pluggable design
  • 3 switch inputs supporting latching and retractive switches
  • 3 sensor inputs supporting occupancy, absence, presence and constant lux control
  • DALI auto addressing
  • DALI automatic replacement detection
  • Bluetooth programming using free Android and iOS app
  • Wireless mesh network for transmission of emergency tests and corridor functions

// NETWORK/////////////////////////////////////////////////////////////////////////////////////////////////

  • Bluetooth 4.2 networking. Auto discoverable with password security.
  • Android and iOS app for configuration and monitoring

// POWER///////////////////////////////////////////////////////////////////////////////////////////////////

  • Wieland GST18i3 female plug
  • Prolojik Part: PC013
  • Wieland Part: GST 18i3 F B2 Z
  • Wieland Order: 92.933.0053.1
  • 16 A 250V rating Screw clamp connections for L,N,E Cable cross section area from 0.5 to 2.5mm

// SWITCH INPUTS//////////////////////////////////////////////////////////////////////////////////////////

  • 3 pole 5mm pitch plug
  • Cable cross section area from 0.5 to 2.5mm

// SENSOR INPUTS//////////////////////////////////////////////////////////////////////////////////////////

  • FCC68 4/4 (RJ11) terminations for 3 sensors
  • Sensor cables available from Prolojik.
  • Prolojik sensor cables are available in 5, 10and 15m lengths

// OUTPUTS/////////////////////////////////////////////////////////////////////////////////////////////////

  • 2 ports Wieland GST18i6 male plug Black/Blue: Prolojik Part: PC016 16 A 250V rating
  • Screw terminal for L,N,E,Em, + and -
  • Cable cross sections from 0.5 to 2.5mm
  • Wieland Order: 92.968.0158.1

// OUTPUTS/////////////////////////////////////////////////////////////////////////////////////////////////

  • 7 ports Wieland GST18i5 male plug Black: Prolojik Part: PC015
  • Screw terminal for L,N,E, + and -
  • Cable cross sections from 0.5 to 2.5mm

Specifications

  • Features
  • Multiple scene setting via I/R remote controller and GS400 sensor or App
  • Reduced Inrush current-1s time delay between group outports at power-up
  • Over-the-air software updates
  • Software configurable input and output function+
  • 9 output lighting control module
  • DALI dimming control
  • Simple integration and wiring
  • Extra low depth for shallow ceiling voids
  • Outputs
  • 3 x independently addressable output groups ports 1-4, 5-7, 8&9
  • Emergency light testing instigation on 2 dedicated ports (2 & 8)
  • Max output per LCM: 6.3A (internally fused)
  • Inputs
  • 3 x low voltage inputs for switch
  • 3 x GS400 multi-sensor inputs
  • Networking
  • Bluetooth 4,2 and Bluetooth mesh networking
  • Cabling and Connectors
  • Mains input
  • Sensor connectors
  • 9 x outputs - Wieland GST18i6 x 2, Wieland GST18i5 x 7
  • Max. Dali dimming load: 100mA
  • Dimensions
  • 250mm x 250mm x 47.5mm (LxWxH)
  • Fixings
  • 4 x 9mm fixing holes (suitable for drop rod and surface mounting)
  • 4 x 7mm holes for drop rod or surface mounting
  • Safety
  • EN 60 950
  • Isolation: 4kV between mains and sensors control
  • Conformity and Standards
  • Generic emission: EN 50 081 part 1
  • Generic immunity: EN 50 082 part 1
  • RFI: EN 55 014
  • DALI 2.0 compliant
  • ARCOM MasterSpec 2013 Classification 29 09 33
  • Environment
  • Storage
  • Temperature: -10°c - +50°c
  • Humidity: 0% - 90% non condensing
  • In Use
  • Temperature: 0°c - +40°c
  • Humidity: 10% - 90% non condensing
  • Mains Input
  • Mains supply: 230Vac +/- 10%; 50Hz
  • Connections: input male socket for PC013 Wieland
  • GST18i3 female plug
  • Plug not included (Available from Prolojik)
  • Sensor & Switch inputs
  • Sensor supply: 12Vdc +/- 5%, 30mA
  • Sensor isolation: 2kV
  • Connection: FCC68 4/4 (RJ11)